Home | Board of Directors | District Map | GMD Act | Rules & Regulations | GMD5 By-Laws | Newsletter | Upcoming Events | Weather Stations | Water Levels | Cathodic Borehole Program | Certified Equipment | Central Kansas Water Banking Association | Rattlesnake Creek Management Plan | Links | Contact Us

 

Certified Equipment Specifications:

 

  Blue Button Bullet  KDA Certified Water Flowmeters List

Check Valves  (K.A.R. 5-6-13a)
 
  (1) An acceptable check valve shall be one that is automatic, quick closing, and seals tightly to prevent the back flow of
water and the substances mixed with water into the source of water supply.
  (2) A check valve shall include the following four components:
      (a) a low pressure drain;
      (b) a vacuum relief device;
      (c) an inspection port; and
      (d) the check valve itself.
  The check valve may consist of four individual components or a manufactured unit that includes all four of the required
components.
  (3) Each check valve shall meet the following standards:
      (a) All components shall be constructed of sturdy corrosion-resistant materials or coated with corrosion-resistant
materials. The body of the unit shall be internally resistant to water of the quality being diverted, the foreign
substances being introduced, and the external environment. All moving parts shall be constructed to operate without
binding, distortion or misalignment.
      (b) The check valve shall contain a suitable, automatic, quick-closing, tight-closing mechanism that closes at the
moment water ceases to flow away from the diversion works. The mechanism shall, by a mechanical force greater
than the weight of the flapper, provide drip-tight closure against reverse flow. The closing force shall be positive and
obvious to hand inspection. This requirement shall not be satisfied by hydraulic back pressure.
      (c) A vacuum relief device, functioning as an air vent, shall be installed between the diversion works and the flapper
in a position that prevents the entry of insects, animals, flood water or other foreign substances into the vacuum relief
device and subsequently the water supply source.
      (d) An automatic low pressure drain shall be installed between the check valve flapper element and the diversion
works, and directly beneath the inspection port at the bottom of the horizontal pipe. The installation shall be made so
that any fluid which seeps past the flapper element towards the diversion works will drain out through the automatic
low pressure drain. The automatic low pressure drain inlet shall not extend inward past the interior pipe wall without
the inclusion of an internal dam or other mechanism to force seepage into the drain. The inlet opening of the drain
shall be at least three fourths of an inch in diameter and the outside discharge point shall be at least two inches above
grade. Any discharge from the drain shall be directed away from the water supply by the natural slope, a pipe, or a
trench.
      (e) An inspection port shall be located between the check valve and the water supply diversion works in a manner
that allows easy access and full visual and hand access to all components of the check valve and assembly
components. The inspection port shall have an orifice or a viewing port of at least four inches in diameter. For
installations with diversion works too small to install a four inch diameter inspection port, the check valve and the
other required components shall be mounted with quick-connect fittings, flange fittings, dresser couplings, or other
fittings designed to allow easy removal and access.
      (f) Systems utilizing a double check valve or reduced-pressure-zone back flow assembly shall be required to adhere,
as a minimum, to a standard equivalent to the manufacturer=s standards or recommendations for a method of
inspection, testing schedule, and rebuilding schedule.
  (4) The check valve and all required components shall be maintained in a satisfactory operating condition that prevents
backflow into the source of water supply any time a foreign substance could reasonably be expected to be introduced into the
water system.
  (5) Variances shall be granted only if a low-pressure drain and vacuum relief device cannot be physically placed in the
system.

                